If a customer wants to know the equipment availability and cabinet capacity, what function of NETECO should he use?
- A . Work Order Management
- B . Energy Efficiency Management
- C . Asset Management
- D . Capacity Management
The main input voltage range of UPS2000-G- (6K-20K) of each capacity model is 80V~280V, and the input frequency range is 40Hz-70Hz. The ultra-wide input range can effectively reduce the number of battery switching, avoid high-incidence areas of faults, reduce the number of battery charging and discharging, and extend battery life.
- A . True
- B . False
Fusionmodule2000’s PAD can be connected to the ECC800 controller via wifi.
- A . True
- B . False
The output power factor of UPS5000-A-400/500K is (), which can adapt to new IT loads and significantly improve the load capacity of the system.
- A . 0.9
- B . 0.95
- C . 0.8
- D . 1
What certifications does Huawei’s precision cabinet have? (Multiple choice)
- A . Earthquake resistance
- B . CE
- C . UL
- D . Thiel
What is the maximum IT load supported by FusionModule2000 integrated UPS?
- A . 125KW
- B . 150KW
- C . 75KW
- D . 50KW
In air-cooled precision air conditioners, the function of the solenoid valve is to prevent refrigerant migration, optimize control, and protect the compressor.
- A . True
- B . False
Using UPS5000-E (50kVA power module), actual load 160kW, rack 1+1 redundancy, single-machine backup solution, 3 groups of batteries per rack, 40 cells per group, the capacity of the main switch box is ()
- A . 250A
- B . 320A
- C . 500A
- D . 630A
The power supply architecture supported by half-cabinet chilled water temperature control ().
- A . Single power supply
- B . Dual power supply
- C . AB are both correct
- D . Others.
In UPS, corresponding to 50k module, the maximum output capacity of a single UPS is ().
- A . 500kVA
- B . 400kVA
- C . 800kVA
- D . 600kVA